C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 86
6.2.4 Single-circuit motocondensing air-based units
PG01 = 1
Single-circuit
PG00 = 7
Motocondensing, air-based
PG00 = 8
Motocondensing, air-based, with cycle
inversion
Analogue inputs
AI 1
(NTC)
- -
AI 2
(NTC)
- -
AI 3
(NTC / 4..20 mA)
Condensing pressure Condensing pressure
AI 4
(NTC / 4.20 mA / DI)
Used as DI 6 Used as DI 6
Digital inputs
DI 1
Fan thermal switch Fan thermal switch
DI 2
Thermal switch compressor # 1 Thermal switch compressor # 1
DI 3
Thermal switch compressor # 2 Thermal switch compressor # 2
DI 4
Compressor 1
st
step control Compressor 1
st
step control
DI 5
Compressor 2
nd
step control Compressor 2
nd
step control
DI 6 (*)
Low-pressure pressure switch Low-pressure pressure switch
Digital outputs
DO 1
- -
DO 2
Compressor # 1 Compressor # 1
DO 3
Compressor # 2 Compressor # 2
DO 4
- Circuit inverter valve
DO 5
- -
DO 6
General alarm General alarm
Analogue outputs
AO 1
(PWM)
Condensing fan Condensing fan
AO 2
(0..10 V / 4..20 mA)
- -
AO 3
(0..10 V / 4..20 mA)
- -
By selecting these units, default values for parameters PC11=2 and PH44=1 are automatically set,
while a “0” value is set for all input/output position parameters not specified in this configuration.
(*) Digital input derived from analogue input (parameter PH44).