C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 139
Cooling
(Chiller),
1=Winter
Heating (Heat
pump)
1284
SetpointEstivo_Attuale 8.5 -15.0 23.0 R/W
1285
SetpointInverno_Attuale 44.0 23.0 70.0 R/W
1286
Abilitazione_FC 0 0 1 R/W
1287
abiReg_FC_ValvolaOnOff 0 0 1 R/W
1288
Setpoint_FreeCooling_Attuale 0.0 -15.0 23.0 R/W
1289
StatoSbrinamento_C1 0 0 8
0=OFF.
1..3=WAIT
4..6=Defrosting
7..8=Dripping
R/W
1290
StatoSbrinamento_C2 0 0 8
0=OFF.
1..3=WAIT
4..6=Defrosting
7..8=Dripping
R/W
1291
PowerRequested 0 0 100 [%] R/W
1292
PowerSupplied 0 0 100 [%] R/W
1293
StatoCompressori[0] 0 0 6 R/W
1294
StatoCompressori[1] 0 0 6 R/W
1295
StatoCompressori[2] 0 0 6 R/W
1296
StatoCompressori[3] 0 0 6 R/W
1297
StatoCompressori[4] 0 0 6 R/W
1298
StatoCompressori[5] 0 0 6 R/W
1299
StatoFan1 0 0 6
0=Disabled,
1=OFF, 2=Wait
ON, 3=ON,
4=Wait OFF,
5=ALL,
6=Manual
R/W
1300
StatoFan2 0 0 6
0=Disabled,
1=OFF, 2=Wait
ON, 3=ON,
4=Wait OFF,
5=ALL,
6=Manual
R/W
1301
StatoPompa1_Ventilatore 0 0 3
0=Disabled,
1=OFF, 2=ON,
3=Alarm
R/W
1302
0 0 3
0=Disabled,
1=OFF, 2=ON,
3=Alarm
R/W
1537
MOdE_ModoFunzionamento 0 0 1
0=Cool
(Chiller),
R/W