C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 76
PH09
It enables the start-up/shutdown of the
machine by supervisor.
No (0) No (0) Yes (1) IS-V
PH10
It enables the change of summer/winter
operating mode via supervisor.
No (0) No (0) Yes (1) IS-V
PH11 Card Modbus address 1 1 247 IS-V
PH12
Card communication baud rate (1=2400,
2=4800, 3=9600, 4=19200)
3 1 4 IS-V
PH13 Modbus parity (0=none, 1=Odd, 2=Even) 2 0 2 IS-V
PH14 Modbus stop bit (0=1 bit, 1=2 bits) 0 0 1 IS-V
PH15 It resets the factory-set parameter defaults. No (0) No (0) Yes (1) IS-V
Wait for the 0
value to be re-
read at the end of
resetting.
PH16
It sets the logic used for the inverting valve.
0: NO – Normally open
1: NC – Normally closed
NO NO (0) NC (1) IS-V
PH17
It sets the logic of digital inputs used in alarm
management.
0: NO – Normally open
1: NC – Normally closed
NC NO (0) NC (1) IS-V
PH18
It sets the logic of the relay used for alarms.
0: NO – Normally open
1: NC – Normally closed
NO NO (0) NC (1) IS-V
PH19
It sets the logic of the digital input used for the
summer/winter commutation.
0: NO – Normally open
1: NC – Normally closed
NO NO (0) NC (1) IS-V
PH20
It sets the logic of the digital input used for
flow control.
0: NO – Normally open
1: NC – Normally closed
NO NO (0) NC (1) IS-V
PH21
It sets the enabling of the probe for ambient
temperature detection (incoming).
Yes (1) No (0) Yes (1) IS-V
PH22
It sets the enabling of the probe for delivery
temperature detection (outgoing) in Circuit #
1.
Yes (1) No (0) Yes (1) IS-V
PH23
It sets the enabling of the probe for delivery
temperature detection (outgoing) in Circuit #
2.
Yes (1) No (0) Yes (1) IS-V
PH24
It sets the enabling of the probe for external
temperature detection.
No (0) No (0) Yes (1) IS-V
PH25
It sets the enabling of the secondary set point
function from digital input.
No (0) No (0) Yes (1) IS-V
PH26
It sets the enabling of the secondary set point
function by a supervisor.
No (0) No (0) Yes (1) IS-V
PH27
It sets the enabling of the dynamic set point
function.
No (0) No (0) Yes (1) IS-V
PH29
It sets the logic of the digital inputs used for
compressor activation:
0: NO – Normally open
1: NC – Normally closed
NO NO (0) NC (1) IS-V
PH31
It sets the type of refrigerant used
(temperature-pressure conversion).
0: No refrigerant
1: R22
2: R134a
3: R404A
4: R407C
5: R410A
6: R507
3
R404A
0 6 IS-V
PH32 It sets the temperature measurement unit: 0 (°C) 0 1 IS-V