EVCO S.p.A. c-pro 3 hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204
page 16 of 52
PGUT = 2
- zone 1 (temperature and humidity).
I/O Description
Zone controller
Analogue inputs
AI 1 External Temperature (NTC)
AI 2 Supply Temperature (NTC)
AI 3 Zone 1 humidity (0-10 V)
AI 4 Zone 1 temperature (NTC)
Serial ports
RS 485 Modbus RTU protocol
CANbus Not used
Digital inputs (potential-free contact ON-OFF)
DI 1 Mixing circuit flow switch
DI 2 Hot block alarm boiler
DI 3 Alarm – cooling block Chiller
DI 4 Remote summer winter
DI 5 Dehumidifiers alarm
Analogue outputs (PWM/0-10V/4-20mA)
AO 1 not available
AO 2 0-10 V flow modulating valve (or 4-20 mA to be ordered)
AO 3 ON-OFF valve (2 or 3 ways) for energy recording
Digital Outputs (Relay)
DO 1 collector_zone 1
DO 2 Dehumidifier collector/dehumidifier consent
DO 3 Hot consent (Boiler or HP)
DO 4 Cold consent (Chiller)
DO 5 Apartment flow line circulation pump control
DO 6 Heating booster control (winter) or for cooling (summer)