Evco EPH4DXP1SA Manual do Utilizador Página 10

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 52
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 9
EVCO S.p.A. c-pro 3 hecto MCSA | User manual ver. 2.0 | Code 144MCSAE204
page 10 of 52
The following tables illustrate the meaning of the connectors.
MODBUS
RS-485 port with Modbus slave communication protocol.
The following drawing illustrates the aspect of the RS-485 port.
The following table illustrates the meaning of the RS-485 port pins.
Pin
Meaning
1 common
2 not connected
3 not connected
4 D0 = B = - (terminal 0 of the transceiver)
5 D1 = A = + (terminal 1 of the transceiver)
6 not connected
7 not connected
8 not connected
The maximum length of the RS-485 port connection cables is 1,000 m (3,280 ft); see also Modbus specifications and
implementation guides Manual (the document is available on the website www.modbus.org).
MICRO-SWITCH
Micro-switch for:
- connecting the termination of the RS-485 port (120 , 0.25 W); position micro switch 1 in the ON position in order to connect
the RS-485 port termination (connect the termination of the first and last network element termination).
Vista de página 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 51 52

Comentários a estes Manuais

Sem comentários