Evco S.p.A. Vroom | Hardware manual ver. 1.00 | Code 114VROOHWE00
page 13 of 22
Parameters PW Timeout 0 240 s 60
Netwok / CAN submenu access password
time-out (after this time without one has operated
with the buttons, to gain access again to the
submenu one has to set the password again)
Parameters Contrast 0 63 - - - 25 Display’s contrast
Parameters Buzz On Key 0 1 - - - 1
Uttering a beep while pressing a button
1 = yes
Parameters PrintLoad. 0 1 - - - 0
Showing the indication Loading . . . while
loading a page
1 = yes
Parameters Print Frame 0 1 - - - 0
Showing frames instead small size pages
1 = yes
Network / CAN MyNode 1 127 - - - 99 Local (or of the interface) CAN node’s address
Network / CAN Master - - - - - - - - - YES The interface always works as master
Network / CAN Baud - - - - - - - - - Auto
CAN communication baud rate
20K = 20,000 baud
50K = 50,000 baud
125K = 125,000 baud
500K = 500.000 baud
Auto = the interface recognizes the baud
rate automatically, on condition
that it is one of the those
mentioned above
One suggests modifying the value of the
parameter and assign each device in the network
the same baud rate.
Network / CAN Net Timeout 1 240 s 5
Remote (or of the devices in the network) CAN
communication time-out (after this time without
CAN communication with a device, this will be
excluded by the network)
Network / CAN NW Node [1] 1 [32] 127 - - - - - -
Remote (or of the devices in the network) CAN
nodes’ address; example for [1] 2:
[1] = node
2 = node’s address
Network /
Modbus
Address 1 247 - - - 1 Modbus address (reserved)