Vista de página 31
C-PRO MEGA HARDWARE MANUAL
Page 32
Lower board 12 VDC + 12 VDC power supply version
Conn.
Letter
code
Description
C1-1 VCC main card power supply (+13Vdc)
C1-2 GND Main power supply reference
JD-1 VDC power supply for active sensors (*1)
JD-2 AI 5 analogic input 5, configurable (NTC, 0..20 mA, 4..20 mA)
JD-3 AI 6 analogic input 6, configurable (NTC, 0..20 mA, 4..20 mA)
JD-4 AI 7 analogic input 7, configurable (NTC, 0..20 mA, 4..20 mA)
JD-5 AI 8 analogic input 8, configurable (NTC, 0..20 mA, 4..20 mA)
JD-6
GND common terminal for analogic inputs
JF-1 COM common terminal for digital inputs
JF-2 DI 3 digital input no. 3 Vac/Vdc
JF-3 DI 4 digital input no. 4 Vac/Vdc
JF-4 DI 5 digital input no. 5 Vac/Vdc
JF-5 DI 6 digital input no. 6 Vac/Vdc
JF-6 COM common terminal for digital inputs
JG-1 COM common terminal for digital inputs
JG-2 DI 7 digital input no. 7 Vac/Vdc
JG-3 DI 8 digital input no. 8 Vac/Vdc
JG-4 DI 9 digital input no. 9 Vac/Vdc
JG-5 DI 10 digital input no. 10 Vac/Vdc
JG-6 COM common terminal for digital inputs
YA-1 VDC connector to power a remote terminal at 12 Vdc
YA-2 CAN1+
CAN + connector Local CAN port
YA-3 CAN1-
CAN - connector Local CAN port
YA-4 GND GND connector Local CAN port
JH-1 NC 1 normally closed contact relay no. 1
JH-2 COM 1 common relay no. 1
JH-3 NO 1 normally open contact relay no. 1
JI-1 NC 2 normally closed contact relay no. 2
JI-2 COM 2 common relay no. 2
JI-3 NO 2 normally open contact relay no. 2
JK-1 COM 3 common for relay no. 3
JK-2 NO 3 normally open contact relay no. 3
JK-3 COM 4 common for relay no. 4
JK-4 NO 4 normally open contact relay no. 4
JK-5 COM 5 common for relay no. 5
JK-6 NO 5 normally open contact relay no. 5
JL-1 COM 6 common relay no. 6
JL-2 NO 6 normally open contact relay no. 6
JL-3 COM 7 common relay no. 7
JL-4 NO 7 normally open contact relay no. 7
JL-5 COM 8 common for relay no. 8
JL-6 NO 8 normally open contact relay no. 8
YB PRG JST connector for programming purposes
C2-1 VCC Not utilized
C2-2 GND Not utilized
*1: VDC=12,5V Imax=200mA (as current sumof all VDC terminals)